Surge arrestor V20 in 75 V, type 2
Surge arrestor V20, 1-pole 75 V
Surge arrestor, type 2
• For surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• Discharge capacity to 40 kA (8/20) per pole through high-performance varistors
• Modular connectable arrestor with dynamic cut-off unit and visual status display
• Locking mechanism with vibration protection and voltage keying
• Halogen-free plastic (UL 94 V-0)
• The remote signalling variants (FS) have a potential-free changeover contact for remote signalling
Application: Equipotential bonding in main and sub-distributions.
| V20175 | |||
| Article number | 5095 14 1 | ||
| SPD to EN 61643-11 | Type 2 | ||
| SPD to IEC 61643-11 | Class II | ||
| SPD to UL 1449 | Type 4 | ||
| Nominal voltage AC (50 / 60 Hz) | Un | V | 60 |
| Maximum continuous voltage AC | UC | V | 75 |
| Nominal discharge current (8/20 μs) | In / L-N | kA | 15 |
| Maximum discharge current (8/20 μs) | Imax | kA | 40 |
| Arrester surge current (8/20 μs) [total] | Itotal | kA | 40 |
| Protection level [L-N] | Up | kV | 0,5 |
| Protection level [L-N] @ 1 kA | Ures | kV | 0,3 |
| Protection level [L-N] @ 5 kA | Ures | kV | 0,35 |
| Max. mains-side overcurrent protection | A gL/gG | 160 | |
| Short-circuit resistance for max. mains-side overcurrent protection | kA | 25 | |
| Operating temperature range | Tu | -40 - +80 °C | |
| Protection rating | IP20 | ||
| Approvals | UL, ÖVE, VDE | ||
| Cable cross-section, flexible (fine-wire) | 1.5 - 35 mm² | ||
| Rigid cable cross-section (single wire/multiwire) | 1.5 - 35 mm² | ||
| Cable cross-section, flexible (fine-wire) | 16 - 2 AWG | ||
| Rigid cable cross-section (single wire/multiwire) | 16 - 2 AWG | ||